SolarBuildListbeta

Truck camper 400W 12V

12V system, designed for a -15C (5F) cold snap - saved 2026-08-16

Clone and edit

Compatibility checks

No issues found by 12 checks11 passed / 0 errors / 0 warnings / 1 note
infoArray is oversized for the controller - output will clip at ~384WArray size vs controller charge output

The array can push 31.3A but the controller tops out at 30A. This is common and usually fine: you harvest more in mornings, evenings, and winter, and the controller simply caps peak output. Verify the controller's max array wattage is not exceeded (separate check).

Array = 200W x 2 panels = 400W
Potential charge current = 400W / 12.8V = 31.3A
Controller rated charge current: 30A
11 passing checks - expand to see the math
passBattery matches the 12V systemSystem voltage coherence

SOK SK12V206P 12V 206Ah Marine (12.8V nominal) is a 12V-class battery.

battery nominal 12.8V is in the 12V class == system 12V
passInverter matches the 12V systemSystem voltage coherence

Victron Energy Phoenix Inverter 12/1200 120V VE.Direct (NEMA 5-15R) DC input is 12V-class.

inverter DC input 12V is in the 12V class == system 12V
passCharge controller supports 12V banksSystem voltage coherence

Victron Energy SmartSolar MPPT 100/30 supports 12/24V battery banks.

controller battery voltages [12, 24] include 12V
passString Voc stays at 48.5V at -15C - cannot reach the 100V limit at any temperatureCold-temperature string voltage

2 x Rich Solar MEGA 200 200W 12V Monocrystalline Solar Panel in series stays below the Victron Energy SmartSolar MPPT 100/30 max PV input voltage at your design low temperature. This string cannot reach 100V at any physically possible temperature.

Why this matters: Panel voltage rises as temperature falls. A string that measures fine in summer can exceed the controller's absolute maximum input voltage on the first cold clear morning, which can permanently destroy the controller - and at these DC power levels, failures can start fires. This is the mistake experienced builders catch most often in DIY parts lists.

Voc_string = Voc x N_series x (1 + tempCoeff/100 x (T_design - 25))
          = 21.80V x 2 x (1 + (-0.28%/100) x (-15 - 25))
          = 21.80V x 2 x 1.1120 = 48.5V
Controller max PV input: 100V
Crossover: string Voc reaches 100V at T = 25 + (100/43.6 - 1) x 100/-0.28 = -437C (below absolute zero - never reached)
passString Vmp 36.8V has healthy margin over the 12V bankMPPT voltage margin

Clears the start floor cold and the hot-weather floor with sag included.

Vmp_string = 18.40V x 2 = 36.8V
Start floor = V_batt + 5V = 12 + 5 = 17V
Hot Vmp (~11% sag) = 36.8V x 0.89 = 32.8V vs hot floor 20V
passArray short-circuit current 11.60A is within the 35A limitArray current vs controller input limit

Within the Victron Energy SmartSolar MPPT 100/30 published max PV short-circuit current.

Isc_array = 11.60A x 1 parallel = 11.60A
Controller max PV short-circuit current: 35A = 35A (manufacturer-specified, compared directly)
passArray 400W is within the controller's 440W rating at 12VMax array wattage for battery voltage

Within the published maximum array wattage.

Array = 200W x 2 panels = 400W
Controller max array wattage at 12V: 440W
passVictron Energy SmartSolar MPPT 100/30 supports LiFePO4 chargingBattery chemistry support

Controller has a lithium profile or user-adjustable charge voltages.

battery chemistry = lifepo4; controller lifepo4_profile = true
passBank BMS limit 170A comfortably covers the inverter's 78.1A drawInverter draw vs battery BMS limit

Healthy headroom at full inverter load.

Inverter draw = 1000W / 12.8V = 78.1A
Bank BMS limit = 170A x 1 batteries = 170A
Headroom band starts at 80% of limit = 136A
passBank BMS peak 200A covers the inverter's 171.9A surgeInverter surge vs battery peak limit

Surge loads within the bank's published peak rating.

Surge draw = 2200W / 12.8V = 171.9A
Bank BMS peak = 200A x 1 batteries = 200A
passCharge current 30A is within the bank's 70A capacityCharge current vs bank capacity

Charge rate within limits.

Controller rated charge = 30A
Bank max charge = manufacturer max charge 70A x 1 = 70A

Parts list

PartQtyEst. priceWhere to buy
Rich Solar MEGA 200 200W 12V Monocrystalline Solar Panel
panel2 in series x 1 stringdatasheet
2$340
Victron Energy SmartSolar MPPT 100/30
controllerdatasheet
1$220
SOK SK12V206P 12V 206Ah Marine
batterydatasheet
1n/a
Victron Energy Phoenix Inverter 12/1200 120V VE.Direct (NEMA 5-15R)
inverterdatasheet
1$393
Estimated total$953(some prices unknown)

Wire and fuse guidance

SegmentContinuousRun (one way)Copper wireV-dropFuse/breaker
Array to charge controller11.6A12 ft14 AWG1.91%15APV-rated (gPV) fuse or DC breaker
Charge controller to battery bank30.0A4 ft8 AWG1.18%40AClass T
Battery bank to inverter78.1A3 ft3 AWG0.72%100AClass T
Array to charge controller: show the math
Continuous current = 11.6A
Design current = 11.6A x 1.25 (NEC continuous) = 14.5A
Wire: 14 AWG copper (75C ampacity 20A); voltage drop 1.91% over 24ft round trip at 36.8V (target <= 3%)
Fuse/breaker: 15A - two criteria, both required:
  carry the load: fuse >= design 14.5A -> next standard size = 15A
  protect the wire: fuse 15A <= 14 AWG ampacity 20A - OK
  construction: PV-rated (gPV) fuse or DC breaker
Charge controller to battery bank: show the math
Continuous current = 30A
Design current = 30A x 1.25 (NEC continuous) = 37.5A
Wire: 8 AWG copper (75C ampacity 50A); voltage drop 1.18% over 8ft round trip at 12.8V (target <= 3%)
Fuse/breaker: 40A - two criteria, both required:
  carry the load: fuse >= design 37.5A -> next standard size = 40A
  protect the wire: fuse 40A <= 8 AWG ampacity 50A - OK
  bank BMS continuous 170A >= fuse 40A: the bank can hold the fuse's rated load
  construction: Class T (interrupt rating matters on battery mains)
Battery bank to inverter: show the math
Continuous current = 78.1A
Design current = 78.1A x 1.25 (NEC continuous) = 97.7A
Wire: 3 AWG copper (75C ampacity 100A); voltage drop 0.72% over 6ft round trip at 12.8V (target <= 3%)
Fuse/breaker: 100A - two criteria, both required:
  carry the load: fuse >= design 97.7A -> next standard size = 100A
  protect the wire: fuse 100A <= 3 AWG ampacity 100A - OK
  bank BMS continuous 170A >= fuse 100A: the bank can hold the fuse's rated load
  construction: Class T (interrupt rating matters on battery mains)

Mount the fuse close to the battery positive terminal - it protects the wire run, so the unprotected stub should be as short as possible.

Sized for 75C copper ampacity with the NEC 1.25 continuous factor and a 3% voltage-drop target. Round up when between sizes and verify against local code.

Balance of system - shopping list

ItemQtyFor
14 AWG copper wire1~30 ft total (12 ft one way, round trip + slack) - Array to charge controller
15A PV-rated (gPV) fuse or DC breaker1Array to charge controller
8 AWG copper wire1~10 ft total (4 ft one way, round trip + slack) - Charge controller to battery bank
40A Class T1Charge controller to battery bank - include the matching fuse holder/block
3 AWG copper wire1~10 ft total (3 ft one way, round trip + slack) - Battery bank to inverter
100A Class T1Battery bank to inverter - include the matching fuse holder/block

Derived from the wire and fuse guidance above. Wire lengths include round trip plus slack - verify against your actual layout, and verify ratings against local code. Buy fuses and wire from reputable electrical suppliers; marketplace listings for these items are a common source of counterfeit or mislabeled parts.

About this build

Slide-in truck campers fight for every pound and cubic inch: the electrical bay is tiny and everything counts against the truck's payload rating. This build keeps the system on 12V - matching the camper's native wiring - and picks components for weight and footprint first. The marine-grade battery is built for the vibration and moisture a camper actually sees.

The compact 1200VA inverter class is a deliberate ceiling: phone and camera charging, a laptop, small appliances. Bigger inverters invite bigger batteries and bigger wire, and the payload budget disappears fast. The roof pair of 200W panels wires in series to keep current low through the roof entry. If you camp mostly where you drive, a DC-DC charger from the truck alternator is the natural next addition - check your alternator's rating before adding one.

Common questions

Rigid or flexible panels on a truck camper?

Flexible panels save weight and follow a curved roof, at some cost in efficiency and lifespan. Rigid panels last longer but need racks and sealed penetrations. On a payload-limited camper the weight argument often wins - this example uses rigid panels, so swap them in the builder if your roof disagrees.

Will the truck's alternator charge this battery?

Not properly on its own - lithium wants a charging profile a raw alternator connection does not provide, and a big lithium bank can work an alternator hard. A DC-DC charger solves both problems and is the standard answer for charge-while-driving.

Why a marine battery in a truck camper?

Camper batteries live a rough life: vibration, temperature swings, occasional moisture. A marine-rated LiFePO4 is built for exactly that environment, and its BMS ratings leave comfortable headroom for this inverter class.