SolarBuildListbeta

Cloning: Budget cabin 12V starter

Pick parts across brands. Every compatibility check shows its math. Save to get a shareable link.

= -13F. Coldest clear morning your site sees; cold raises panel voltage.

Solar array

Panels + how they are wired (series x parallel)

Rich Solar MEGA 200 200W 12V Monocrystalline Solar Panel
200W, Voc 21.8V, Isc 11.6A
4 panels, 800W total

Charge controller

MPPT/PWM between array and battery

Renogy Rover 60A
MPPT, 140V max PV, 60A, 12/24/36/48V banks

Battery bank

Identical batteries in parallel

Renogy Core Mini 12V 100Ah
12.8V 100Ah LIFEPO4, BMS 100A
2.6 kWh total

Inverter / all-in-one

DC to AC. All-in-one units include the charge controller.

Renogy 2000W 12V Pure Sine Wave Inverter (RNG-INVT-2000-12V-P2)
inverter, 12V, 2000W (4000W surge)

Wire runs

One-way distances for wire and fuse sizing.

SegmentContinuousRun (one way)Copper wireV-dropFuse/breaker
Array to charge controller23.2A25 ft8 AWG1.98%30APV-rated (gPV) fuse or DC breaker
Charge controller to battery bank60.0A5 ft4 AWG1.16%80AClass T
Battery bank to inverter156.3A4 ft3/0 AWG0.60%200AClass T
Array to charge controller: show the math
Continuous current = 23.2A
Design current = 23.2A x 1.25 (NEC continuous) = 29A
Wire: 8 AWG copper (75C ampacity 50A); voltage drop 1.98% over 50ft round trip at 36.8V (target <= 3%)
Fuse/breaker: 30A - two criteria, both required:
  carry the load: fuse >= design 29A -> next standard size = 30A
  protect the wire: fuse 30A <= 8 AWG ampacity 50A - OK
  construction: PV-rated (gPV) fuse or DC breaker
Charge controller to battery bank: show the math
Continuous current = 60A
Design current = 60A x 1.25 (NEC continuous) = 75A
Wire: 4 AWG copper (75C ampacity 85A); voltage drop 1.16% over 10ft round trip at 12.8V (target <= 3%)
Fuse/breaker: 80A - two criteria, both required:
  carry the load: fuse >= design 75A -> next standard size = 80A
  protect the wire: fuse 80A <= 4 AWG ampacity 85A - OK
  bank BMS continuous 200A >= fuse 80A: the bank can hold the fuse's rated load
  construction: Class T (interrupt rating matters on battery mains)
Battery bank to inverter: show the math
Continuous current = 156.3A
Design current = 156.3A x 1.25 (NEC continuous) = 195.3A
Wire: 3/0 AWG copper (75C ampacity 200A); voltage drop 0.60% over 8ft round trip at 12.8V (target <= 3%)
Fuse/breaker: 200A - two criteria, both required:
  carry the load: fuse >= design 195.3A -> next standard size = 200A
  protect the wire: fuse 200A <= 3/0 AWG ampacity 200A - OK
  bank BMS continuous 200A >= fuse 200A: the bank can hold the fuse's rated load
  construction: Class T (interrupt rating matters on battery mains)

Mount the fuse close to the battery positive terminal - it protects the wire run, so the unprotected stub should be as short as possible.

Sized for 75C copper ampacity with the NEC 1.25 continuous factor and a 3% voltage-drop target. Round up when between sizes and verify against local code.

Balance of system - shopping list

ItemQtyFor
8 AWG copper wire1~60 ft total (25 ft one way, round trip + slack) - Array to charge controller
30A PV-rated (gPV) fuse or DC breaker1Array to charge controller
4 AWG copper wire1~15 ft total (5 ft one way, round trip + slack) - Charge controller to battery bank
80A Class T1Charge controller to battery bank - include the matching fuse holder/block
3/0 AWG copper wire1~10 ft total (4 ft one way, round trip + slack) - Battery bank to inverter
200A Class T1Battery bank to inverter - include the matching fuse holder/block

Derived from the wire and fuse guidance above. Wire lengths include round trip plus slack - verify against your actual layout, and verify ratings against local code. Buy fuses and wire from reputable electrical suppliers; marketplace listings for these items are a common source of counterfeit or mislabeled parts.

Parts list

PartQtyEst. priceWhere to buy
Rich Solar MEGA 200 200W 12V Monocrystalline Solar Panel
panel2 in series x 2 stringsdatasheet
4$680
Renogy Rover 60A
controllerdatasheet
1$260
Renogy Core Mini 12V 100Ah
batterydatasheet
2$534
Renogy 2000W 12V Pure Sine Wave Inverter (RNG-INVT-2000-12V-P2)
inverterdatasheet
1$369.99
Estimated total$1,843.99
No issues found by 11 checks10 passed / 0 errors / 0 warnings / 1 note / 2 not checkable
infoArray is oversized for the controller - output will clip at ~768WArray size vs controller charge output

The array can push 62.5A but the controller tops out at 60A. This is common and usually fine: you harvest more in mornings, evenings, and winter, and the controller simply caps peak output. Verify the controller's max array wattage is not exceeded (separate check).

Array = 200W x 4 panels = 800W
Potential charge current = 800W / 12.8V = 62.5A
Controller rated charge current: 60A
10 passing checks - expand to see the math
passBattery matches the 12V systemSystem voltage coherence

Renogy Core Mini 12V 100Ah (12.8V nominal) is a 12V-class battery.

battery nominal 12.8V is in the 12V class == system 12V
passInverter matches the 12V systemSystem voltage coherence

Renogy 2000W 12V Pure Sine Wave Inverter (RNG-INVT-2000-12V-P2) DC input is 12V-class.

inverter DC input 12V is in the 12V class == system 12V
passCharge controller supports 12V banksSystem voltage coherence

Renogy Rover 60A supports 12/24/36/48V battery banks.

controller battery voltages [12, 24, 36, 48] include 12V
passString Voc stays at 49.7V at -25C - cannot reach the 140V limit at any temperatureCold-temperature string voltage

2 x Rich Solar MEGA 200 200W 12V Monocrystalline Solar Panel in series stays below the Renogy Rover 60A max PV input voltage at your design low temperature. This string cannot reach 140V at any physically possible temperature.

Why this matters: Panel voltage rises as temperature falls. A string that measures fine in summer can exceed the controller's absolute maximum input voltage on the first cold clear morning, which can permanently destroy the controller - and at these DC power levels, failures can start fires. This is the mistake experienced builders catch most often in DIY parts lists.

Voc_string = Voc x N_series x (1 + tempCoeff/100 x (T_design - 25))
          = 21.80V x 2 x (1 + (-0.28%/100) x (-25 - 25))
          = 21.80V x 2 x 1.1400 = 49.7V
Controller max PV input: 140V
Crossover: string Voc reaches 140V at T = 25 + (140/43.6 - 1) x 100/-0.28 = -764.6C (below absolute zero - never reached)
passString Vmp 36.8V has healthy margin over the 12V bankMPPT voltage margin

Clears the start floor cold and the hot-weather floor with sag included.

Vmp_string = 18.40V x 2 = 36.8V
Start floor = V_batt + 5V = 12 + 5 = 17V
Hot Vmp (~11% sag) = 36.8V x 0.89 = 32.8V vs hot floor 20V
passArray 800W is within the controller's 800W rating at 12VMax array wattage for battery voltage

Within the published maximum array wattage.

Array = 200W x 4 panels = 800W
Controller max array wattage at 12V: 800W
passRenogy Rover 60A supports LiFePO4 chargingBattery chemistry support

Controller has a lithium profile or user-adjustable charge voltages.

battery chemistry = lifepo4; controller lifepo4_profile = true
passBank BMS limit 200A comfortably covers the inverter's 156.3A drawInverter draw vs battery BMS limit

Healthy headroom at full inverter load.

Inverter draw = 2000W / 12.8V = 156.3A
Bank BMS limit = 100A x 2 batteries = 200A
Headroom band starts at 80% of limit = 160A
passBank BMS peak 600A covers the inverter's 312.5A surgeInverter surge vs battery peak limit

Surge loads within the bank's published peak rating.

Surge draw = 4000W / 12.8V = 312.5A
Bank BMS peak = 300A x 2 batteries = 600A
passCharge current 60A is within the bank's 200A capacityCharge current vs bank capacity

Charge rate within limits.

Controller rated charge = 60A
Bank max charge = manufacturer max charge 100A x 2 = 200A
2 checks not run (missing published specs)
not checkedNot checkedArray current vs controller input limit

Renogy Rover 60A does not publish a PV input current limit in our data. MPPT controllers generally current-limit safely, but verify against the manual.

not checkedNot checkedBattery parallel count

Renogy Core Mini 12V 100Ah does not publish a max parallel count in our data. Verify with the manufacturer before paralleling 2 units.

Saving creates a permanent link you can post anywhere. No account needed.