SolarBuildListbeta

Cloning: Full-time vanlife 800W 24V

Pick parts across brands. Every compatibility check shows its math. Save to get a shareable link.

= 14F. Coldest clear morning your site sees; cold raises panel voltage.

Solar array

Panels + how they are wired (series x parallel)

Rich Solar MEGA 200 200W 12V Monocrystalline Solar Panel
200W, Voc 21.8V, Isc 11.6A
4 panels, 800W total

Charge controller

MPPT/PWM between array and battery

Victron Energy SmartSolar MPPT 100/50
MPPT, 100V max PV, 50A, 12/24V banks

Battery bank

Identical batteries in parallel

LiTime 24V 100Ah LiFePO4
25.6V 100Ah LIFEPO4, BMS 100A
5.1 kWh total

Inverter / all-in-one

DC to AC. All-in-one units include the charge controller.

Victron Energy MultiPlus-II 24/3000/70-50 120V
inverter/charger, 24V, 2400W (5500W surge)

Wire runs

One-way distances for wire and fuse sizing.

SegmentContinuousRun (one way)Copper wireV-dropFuse/breaker
Array to charge controller23.2A20 ft10 AWG2.52%30APV-rated (gPV) fuse or DC breaker
Charge controller to battery bank50.0A5 ft6 AWG0.77%70AClass T
Battery bank to inverter93.8A5 ft1 AWG0.45%125AClass T
Array to charge controller: show the math
Continuous current = 23.2A
Design current = 23.2A x 1.25 (NEC continuous) = 29A
Wire: 10 AWG copper (75C ampacity 35A); voltage drop 2.52% over 40ft round trip at 36.8V (target <= 3%)
Fuse/breaker: 30A - two criteria, both required:
  carry the load: fuse >= design 29A -> next standard size = 30A
  protect the wire: fuse 30A <= 10 AWG ampacity 35A - OK
  construction: PV-rated (gPV) fuse or DC breaker
Charge controller to battery bank: show the math
Continuous current = 50A
Design current = 50A x 1.25 (NEC continuous) = 62.5A
Wire: 6 AWG copper (75C ampacity 65A); voltage drop 0.77% over 10ft round trip at 25.6V (target <= 3%)
Fuse/breaker: 70A - two criteria, both required:
  carry the load: fuse >= design 62.5A -> next standard size = 70A
  protect the wire: fuse 70A <= 6 AWG ampacity 65A - NOT satisfied, upsize the wire
  bank BMS continuous 200A >= fuse 70A: the bank can hold the fuse's rated load
  construction: Class T (interrupt rating matters on battery mains)
Battery bank to inverter: show the math
Continuous current = 93.8A
Design current = 93.8A x 1.25 (NEC continuous) = 117.2A
Wire: 1 AWG copper (75C ampacity 130A); voltage drop 0.45% over 10ft round trip at 25.6V (target <= 3%)
Fuse/breaker: 125A - two criteria, both required:
  carry the load: fuse >= design 117.2A -> next standard size = 125A
  protect the wire: fuse 125A <= 1 AWG ampacity 130A - OK
  bank BMS continuous 200A >= fuse 125A: the bank can hold the fuse's rated load
  construction: Class T (interrupt rating matters on battery mains)

Mount the fuse close to the battery positive terminal - it protects the wire run, so the unprotected stub should be as short as possible.

Sized for 75C copper ampacity with the NEC 1.25 continuous factor and a 3% voltage-drop target. Round up when between sizes and verify against local code.

Balance of system - shopping list

ItemQtyFor
10 AWG copper wire1~45 ft total (20 ft one way, round trip + slack) - Array to charge controller
30A PV-rated (gPV) fuse or DC breaker1Array to charge controller
6 AWG copper wire1~15 ft total (5 ft one way, round trip + slack) - Charge controller to battery bank
70A Class T1Charge controller to battery bank - include the matching fuse holder/block
1 AWG copper wire1~15 ft total (5 ft one way, round trip + slack) - Battery bank to inverter
125A Class T1Battery bank to inverter - include the matching fuse holder/block

Derived from the wire and fuse guidance above. Wire lengths include round trip plus slack - verify against your actual layout, and verify ratings against local code. Buy fuses and wire from reputable electrical suppliers; marketplace listings for these items are a common source of counterfeit or mislabeled parts.

Parts list

PartQtyEst. priceWhere to buy
Rich Solar MEGA 200 200W 12V Monocrystalline Solar Panel
panel2 in series x 2 stringsdatasheet
4$680
Victron Energy SmartSolar MPPT 100/50
controllerdatasheet
1$300
LiTime 24V 100Ah LiFePO4
batterydatasheet
2$1,000
Victron Energy MultiPlus-II 24/3000/70-50 120V
inverterdatasheet
1$997
Estimated total$2,977
No issues found by 14 checks14 passed / 0 errors / 0 warnings / 0 notes / 1 not checkable
14 passing checks - expand to see the math
passBattery matches the 24V systemSystem voltage coherence

LiTime 24V 100Ah LiFePO4 (25.6V nominal) is a 24V-class battery.

battery nominal 25.6V is in the 24V class == system 24V
passInverter matches the 24V systemSystem voltage coherence

Victron Energy MultiPlus-II 24/3000/70-50 120V DC input is 24V-class.

inverter DC input 24V is in the 24V class == system 24V
passCharge controller supports 24V banksSystem voltage coherence

Victron Energy SmartSolar MPPT 100/50 supports 12/24V battery banks.

controller battery voltages [12, 24] include 24V
passString Voc stays at 47.9V at -10C - cannot reach the 100V limit at any temperatureCold-temperature string voltage

2 x Rich Solar MEGA 200 200W 12V Monocrystalline Solar Panel in series stays below the Victron Energy SmartSolar MPPT 100/50 max PV input voltage at your design low temperature. This string cannot reach 100V at any physically possible temperature.

Why this matters: Panel voltage rises as temperature falls. A string that measures fine in summer can exceed the controller's absolute maximum input voltage on the first cold clear morning, which can permanently destroy the controller - and at these DC power levels, failures can start fires. This is the mistake experienced builders catch most often in DIY parts lists.

Voc_string = Voc x N_series x (1 + tempCoeff/100 x (T_design - 25))
          = 21.80V x 2 x (1 + (-0.28%/100) x (-10 - 25))
          = 21.80V x 2 x 1.0980 = 47.9V
Controller max PV input: 100V
Crossover: string Voc reaches 100V at T = 25 + (100/43.6 - 1) x 100/-0.28 = -437C (below absolute zero - never reached)
passString Vmp 36.8V has healthy margin over the 24V bankMPPT voltage margin

Clears the start floor cold and the hot-weather floor with sag included.

Vmp_string = 18.40V x 2 = 36.8V
Start floor = V_batt + 5V = 24 + 5 = 29V
Hot Vmp (~11% sag) = 36.8V x 0.89 = 32.8V vs hot floor 32V
passArray short-circuit current 23.20A is within the 60A limitArray current vs controller input limit

Within the Victron Energy SmartSolar MPPT 100/50 published max PV short-circuit current.

Isc_array = 11.60A x 2 parallel = 23.20A
Controller max PV short-circuit current: 60A = 60A (manufacturer-specified, compared directly)
passController can pass the array's full output (31.3A of 50A rated)Array size vs controller charge output

No clipping at rated conditions.

Array = 200W x 4 panels = 800W
Potential charge current = 800W / 25.6V = 31.3A
Controller rated charge current: 50A
passArray 800W is within the controller's 1400W rating at 24VMax array wattage for battery voltage

Within the published maximum array wattage.

Array = 200W x 4 panels = 800W
Controller max array wattage at 24V: 1400W
passVictron Energy SmartSolar MPPT 100/50 supports LiFePO4 chargingBattery chemistry support

Controller has a lithium profile or user-adjustable charge voltages.

battery chemistry = lifepo4; controller lifepo4_profile = true
passVictron Energy MultiPlus-II 24/3000/70-50 120V charger supports LiFePO4Battery chemistry support

Inverter/charger has a lithium charge profile.

battery chemistry = lifepo4; inverter charger lifepo4_profile = true
passBank BMS limit 200A comfortably covers the inverter's 93.8A drawInverter draw vs battery BMS limit

Healthy headroom at full inverter load.

Inverter draw = 2400W / 25.6V = 93.8A
Bank BMS limit = 100A x 2 batteries = 200A
Headroom band starts at 80% of limit = 160A
passBank BMS peak 560A covers the inverter's 214.8A surgeInverter surge vs battery peak limit

Surge loads within the bank's published peak rating.

Surge draw = 5500W / 25.6V = 214.8A
Bank BMS peak = 280A x 2 batteries = 560A
pass2 in parallel is within the manufacturer limit of 4Battery parallel count

Supported parallel configuration.

2 in parallel vs manufacturer max 4
passCharge current 50A is within the bank's 200A capacityCharge current vs bank capacity

Charge rate within limits.

Controller rated charge = 50A
Bank max charge = manufacturer max charge 100A x 2 = 200A
1 check not run (missing published specs)
not checkedNot checkedClosed-loop battery communications

Comms protocols for LiTime 24V 100Ah LiFePO4 are not in our data. The system will still work open-loop with manually set charge voltages.

Saving creates a permanent link you can post anywhere. No account needed.