Cloning: Weekender van 400W 12V
Pick parts across brands. Every compatibility check shows its math. Save to get a shareable link.
Solar array
Panels + how they are wired (series x parallel)
Charge controller
MPPT/PWM between array and battery
Battery bank
Identical batteries in parallel
Inverter / all-in-one
DC to AC. All-in-one units include the charge controller.
Wire runs
One-way distances for wire and fuse sizing.
| Segment | Continuous | Run (one way) | Copper wire | V-drop | Fuse/breaker |
|---|---|---|---|---|---|
| Array to charge controller | 11.6A | 15 ft | 14 AWG | 2.39% | 15APV-rated (gPV) fuse or DC breaker |
| Charge controller to battery bank | 30.0A | 5 ft | 8 AWG | 1.47% | 40AClass T |
| Battery bank to inverter | 78.1A | 3 ft | 3 AWG | 0.72% | 100AClass T |
Array to charge controller: show the math
Continuous current = 11.6A Design current = 11.6A x 1.25 (NEC continuous) = 14.5A Wire: 14 AWG copper (75C ampacity 20A); voltage drop 2.39% over 30ft round trip at 36.8V (target <= 3%) Fuse/breaker: 15A - two criteria, both required: carry the load: fuse >= design 14.5A -> next standard size = 15A protect the wire: fuse 15A <= 14 AWG ampacity 20A - OK construction: PV-rated (gPV) fuse or DC breaker
Charge controller to battery bank: show the math
Continuous current = 30A Design current = 30A x 1.25 (NEC continuous) = 37.5A Wire: 8 AWG copper (75C ampacity 50A); voltage drop 1.47% over 10ft round trip at 12.8V (target <= 3%) Fuse/breaker: 40A - two criteria, both required: carry the load: fuse >= design 37.5A -> next standard size = 40A protect the wire: fuse 40A <= 8 AWG ampacity 50A - OK bank BMS continuous 200A >= fuse 40A: the bank can hold the fuse's rated load construction: Class T (interrupt rating matters on battery mains)
Battery bank to inverter: show the math
Continuous current = 78.1A Design current = 78.1A x 1.25 (NEC continuous) = 97.7A Wire: 3 AWG copper (75C ampacity 100A); voltage drop 0.72% over 6ft round trip at 12.8V (target <= 3%) Fuse/breaker: 100A - two criteria, both required: carry the load: fuse >= design 97.7A -> next standard size = 100A protect the wire: fuse 100A <= 3 AWG ampacity 100A - OK bank BMS continuous 200A >= fuse 100A: the bank can hold the fuse's rated load construction: Class T (interrupt rating matters on battery mains)
Mount the fuse close to the battery positive terminal - it protects the wire run, so the unprotected stub should be as short as possible.
Sized for 75C copper ampacity with the NEC 1.25 continuous factor and a 3% voltage-drop target. Round up when between sizes and verify against local code.
Balance of system - shopping list
| Item | Qty | For |
|---|---|---|
| 14 AWG copper wire | 1 | ~35 ft total (15 ft one way, round trip + slack) - Array to charge controller |
| 15A PV-rated (gPV) fuse or DC breaker | 1 | Array to charge controller |
| 8 AWG copper wire | 1 | ~15 ft total (5 ft one way, round trip + slack) - Charge controller to battery bank |
| 40A Class T | 1 | Charge controller to battery bank - include the matching fuse holder/block |
| 3 AWG copper wire | 1 | ~10 ft total (3 ft one way, round trip + slack) - Battery bank to inverter |
| 100A Class T | 1 | Battery bank to inverter - include the matching fuse holder/block |
Derived from the wire and fuse guidance above. Wire lengths include round trip plus slack - verify against your actual layout, and verify ratings against local code. Buy fuses and wire from reputable electrical suppliers; marketplace listings for these items are a common source of counterfeit or mislabeled parts.
Parts list
| Part | Qty | Est. price | Where to buy |
|---|---|---|---|
Rich Solar MEGA 200 200W 12V Monocrystalline Solar Panel | 2 | $340 | |
Victron Energy SmartSolar MPPT 100/30 controllerdatasheet | 1 | $220 | |
LiTime 12V 230Ah Plus LiFePO4 batterydatasheet | 1 | $520 | |
Renogy 1000W 12V Pure Sine Wave Inverter (RNG-INVT-1000-12V-P2) inverterdatasheet | 1 | $175.99 | |
| Estimated total | $1,255.99 |
infoArray is oversized for the controller - output will clip at ~384WArray size vs controller charge output
The array can push 31.3A but the controller tops out at 30A. This is common and usually fine: you harvest more in mornings, evenings, and winter, and the controller simply caps peak output. Verify the controller's max array wattage is not exceeded (separate check).
Array = 200W x 2 panels = 400W Potential charge current = 400W / 12.8V = 31.3A Controller rated charge current: 30A
11 passing checks - expand to see the math
passBattery matches the 12V systemSystem voltage coherence
LiTime 12V 230Ah Plus LiFePO4 (12.8V nominal) is a 12V-class battery.
battery nominal 12.8V is in the 12V class == system 12V
passInverter matches the 12V systemSystem voltage coherence
Renogy 1000W 12V Pure Sine Wave Inverter (RNG-INVT-1000-12V-P2) DC input is 12V-class.
inverter DC input 12V is in the 12V class == system 12V
passCharge controller supports 12V banksSystem voltage coherence
Victron Energy SmartSolar MPPT 100/30 supports 12/24V battery banks.
controller battery voltages [12, 24] include 12V
passString Voc stays at 47.9V at -10C - cannot reach the 100V limit at any temperatureCold-temperature string voltage
2 x Rich Solar MEGA 200 200W 12V Monocrystalline Solar Panel in series stays below the Victron Energy SmartSolar MPPT 100/30 max PV input voltage at your design low temperature. This string cannot reach 100V at any physically possible temperature.
Why this matters: Panel voltage rises as temperature falls. A string that measures fine in summer can exceed the controller's absolute maximum input voltage on the first cold clear morning, which can permanently destroy the controller - and at these DC power levels, failures can start fires. This is the mistake experienced builders catch most often in DIY parts lists.
Voc_string = Voc x N_series x (1 + tempCoeff/100 x (T_design - 25))
= 21.80V x 2 x (1 + (-0.28%/100) x (-10 - 25))
= 21.80V x 2 x 1.0980 = 47.9V
Controller max PV input: 100V
Crossover: string Voc reaches 100V at T = 25 + (100/43.6 - 1) x 100/-0.28 = -437C (below absolute zero - never reached)passString Vmp 36.8V has healthy margin over the 12V bankMPPT voltage margin
Clears the start floor cold and the hot-weather floor with sag included.
Vmp_string = 18.40V x 2 = 36.8V Start floor = V_batt + 5V = 12 + 5 = 17V Hot Vmp (~11% sag) = 36.8V x 0.89 = 32.8V vs hot floor 20V
passArray short-circuit current 11.60A is within the 35A limitArray current vs controller input limit
Within the Victron Energy SmartSolar MPPT 100/30 published max PV short-circuit current.
Isc_array = 11.60A x 1 parallel = 11.60A Controller max PV short-circuit current: 35A = 35A (manufacturer-specified, compared directly)
passArray 400W is within the controller's 440W rating at 12VMax array wattage for battery voltage
Within the published maximum array wattage.
Array = 200W x 2 panels = 400W Controller max array wattage at 12V: 440W
passVictron Energy SmartSolar MPPT 100/30 supports LiFePO4 chargingBattery chemistry support
Controller has a lithium profile or user-adjustable charge voltages.
battery chemistry = lifepo4; controller lifepo4_profile = true
passBank BMS limit 200A comfortably covers the inverter's 78.1A drawInverter draw vs battery BMS limit
Healthy headroom at full inverter load.
Inverter draw = 1000W / 12.8V = 78.1A Bank BMS limit = 200A x 1 batteries = 200A Headroom band starts at 80% of limit = 160A
passBank BMS peak 600A covers the inverter's 156.3A surgeInverter surge vs battery peak limit
Surge loads within the bank's published peak rating.
Surge draw = 2000W / 12.8V = 156.3A Bank BMS peak = 600A x 1 batteries = 600A
passCharge current 30A is within the bank's 200A capacityCharge current vs bank capacity
Charge rate within limits.
Controller rated charge = 30A Bank max charge = manufacturer max charge 200A x 1 = 200A
Saving creates a permanent link you can post anywhere. No account needed.